Do Florida assisted living facilities have to have a generator?

Yes, in practice. Rule 59A-36.025 requires every Florida ALF to have an alternate power source, such as a generator, plus fuel to keep a cooled area at or below 81 degrees Fahrenheit for at least 96 hours after losing power. In Palm Beach County, 119 of 197 licensed ALFs report a fixed generator.

Reviewed Nov 26, 2026
Key facts
StandardCooled area at or below 81 degrees Fahrenheit for at least 96 hours after loss of primary power
Fuel on site48 hours (16 beds or fewer) or 72 hours (17 or more); 96 hours secured in a declared emergency
Approved byThe county emergency management agency
In force sinceMarch 26, 2018, as Rule 58A-5.036; now 59A-36.025, amended Nov 23, 2023
Palm Beach119 of 197 report a fixed generator; 112 say it supports air conditioning (AHCA, Nov 26, 2026)

What does Florida's generator rule require?

Rule 59A-36.025, Emergency Environmental Control for Assisted Living Facilities, covers every ALF, whatever its size:

The acquisition of a sufficient alternate power source such as a generator(s), maintained at the assisted living facility, to ensure that current licensees of assisted living facilities will be equipped to ensure ambient air temperatures will be maintained at or below 81 degrees Fahrenheit for a minimum of ninety-six (96) hours in the event of the loss of primary electrical power.

Rule 59A-36.025(1)(a), F.A.C.
  • The cooled area can be part of the building: 20 net square feet per resident, sized for 80 percent of licensed beds.
  • Any system or equipment qualifies if the area stays at or below 81 degrees for 96 hours.
  • In an evacuation zone, the power source and fuel stay on hand while residents are there; a mobile generator may travel with them if they evacuate.
  • A multistory building that moves residents upstairs in a flood or surge must put power equipment where flooding and surge cannot damage it.
  • The plan covers equipment maintenance and testing, and a carbon monoxide alarm.

Want three Palm Beach County options with their records?

Tell us what your parent needs. ALFCheck emails three communities that fit, each with its full state record. Free to families.

Get my free shortlistNo call list. A community learns your name only when you choose to tour it.

Fuel on site depends on the number of beds

1. Facilities must store minimum amounts of fuel onsite as follows:

a. A facility with a licensed capacity of 16 beds or less must store 48 hours of fuel onsite.

b. A facility with a licensed capacity of 17 or more beds must store 72 hours of fuel onsite.

Rule 59A-36.025(1)(b)1., F.A.C.
SituationWhat the rule requires
Licensed for 16 beds or fewer48 hours of fuel on site
Licensed for 17 or more beds72 hours of fuel on site
Declared state of emergency that may affect power96 hours of fuel secured; portable containers may hold the rest
Piped natural gasAllowed, and meets the on-site fuel requirement
Local limits on fuel storageStore the most allowed, with a reliable way to get more at least 24 hours before running out

The plan names the fuel source and storage spot, placed where local zoning and the Florida Building Code allow. Ask how long the fuel lasts at the real load, air conditioning included. Lights and refrigerators alone do not meet the standard.

The county approves the plan, not AHCA

The power plan supplements the facility's comprehensive emergency management plan:

The comprehensive emergency management plan is subject to review and approval by the county emergency management agency.

The county emergency management agency shall complete its review within 60 days and either approve the plan or advise the facility of necessary revisions.

Fla. Stat. 429.41(1)(b)

Under Rule 59A-36.019 the county, here Palm Beach County's emergency management agency, is the final authority. Plans go in every year, and significant changes within 30 days. After approval:

  • The facility sends AHCA proof within 30 days.
  • AHCA posts a consumer-friendly summary within 10 business days.
  • Residents and legal representatives get written notice within 5 business days of first submission, and again when the plan is fully in place. Yearly re-approvals need none unless the plan changed significantly.

What do Palm Beach County's records show?

78 of 197 licensed ALFs do not report a fixed generator on their AHCA emergency power profile. That is not a violation, since the rule allows other systems. Ask what keeps your mother's room at 81 degrees or below on day three without power.

Planning is the weak spot. Emergency management planning was the county's most-cited area in 36 months of inspections, at 62 facilities. AHCA files it apart from emergency cooling and power, so a working generator does not prevent a plan citation.

AHCA's Generator Status Map, on its Emergency Preparedness Resources page, shows which nursing homes and ALFs comply with the power rules, by county, facility type and status. ALFCheck records show the AHCA power fields beside the inspections.

In Palm Beach County

119 of 197 licensed ALFs report a fixed generator, and 112 say emergency power supports air conditioning (AHCA, Nov 26, 2026).

See every facility's power details

Questions to ask about emergency power

Get answers in writing. If the facility hesitates, ask for its AHCA consumer summary and last county approval date.

  1. Where is the cooled area, how big, and for how many residents?
  2. What runs on backup power: central air or a few rooms, medication refrigerators, elevators, oxygen concentrators?
  3. How many hours of fuel are on site today, and how do you get more in a declared emergency?
  4. When was the generator last tested and serviced, and by whom?
  5. When did the county last approve your plan?
  6. Are you in an evacuation zone? If you evacuate, where to, how, and with which staff?
  7. Who calls me after a storm?
  8. Who checks residents for dehydration and heat illness during an outage, and how often?

Written procedures must cover cooling devices, ice and refrigeration for medicines, staff checks for dehydration and heat injury, and calling emergency services. You can read them:

The written policies and procedures must be readily available for inspection by each resident; each resident’s legal representative, designee, surrogate, guardian, attorney in fact, or case manager; each resident’s estate; and such additional parties as authorized in writing or by law.

Rule 59A-36.025(5)(c), F.A.C.

Common questions

When did Florida start requiring ALF generators?

After Hurricane Irma: an emergency rule on September 16, 2017, then AHCA's October 12, 2017 statement giving nursing homes and ALFs 60 days from publication to have working generators and 96 hours of fuel. The permanent ALF rule took effect March 26, 2018 as Rule 58A-5.036, moved to 59A-36.025 on July 1, 2019, and was amended November 23, 2023.

What happens to a facility that breaks the generator rule?

Under Rule 59A-36.025(6), AHCA may seek any remedy in chapter 429, part I, or chapter 408, part II, including license revocation, license suspension and fines.

When do the 96 hours start counting?

From the loss of primary electrical power, not from when a storm is forecast or a watch is issued.

Where does the facility keep its plan?

At its physical address. Readily available means the facility can produce it immediately, on paper or on screen, when an authorized reviewer asks.

Choosing assisted living in Palm Beach County?

ALFCheck emails three communities that fit your parent, each with its full state record. Free to families. No call list.